Warning: Invalid argument supplied for foreach() in /home/fogosauga/domains/fogo.lt/public_html/en/wp-includes/shortcodes.php on line 625

Fire protection of Steel Constructions

Steel – inorganic building material classified as non-flammable (flammability class A1 / A2), but the steel structure loses its bearing properties (deformation) during fire when temperature reaches approximately 450 – 500 ° C. This process takes less than 10 minutes. During Fire resistance tests temperature is increased according standard fire spread curve (ISO), 550°C temperature is reached in just 5 minutes, 850°C – 30 minutes. In 90 minutes – approximately 1000°C. In order to keep best qualities of steel construction, it is necessary to perform quality and reliable protection from fire.

Protection by Intumescent painting

We increase the fire resistance of steel constructions by applying fire protective, intumescent paint. For this purpose, we use water or solvent based intumescent paints FLAME STAL or PROMAPAINT. Depending on the corrosive classes, we recommend to apply additional layer of top coat on already fire protected steel constructions.

Intumescent paint cannot be used for all fire resistance classes. Classes, higher than one hour, usually have to be protected by other means, systems. In such cases, the steel structures should be protected by so called „Constructive measures“. These are Soft type systems (special mineral wool slabs) or Hard type systems (calcium silicate based panels). Steel structures can be protected up to class R240 of fire resistance.

We also perform steel construction corrosion protective painting, old protective coating renovation works.Works are carried out exclusively with certified protective materials / systems.

Protection by installing Calcium-sylicate or Mineral wool boards

We provide works for increasing fire resistance of steel structure by covering their surface with Calcium silicate boards Promatect (hard system) or with special mineral wool panels (soft system). Depending on situation constructions can be provided with 2, 3 or 4 – sided protection.

Our specialists will provide the customer with an ergonomic solution by offering measures in order to fulfill the designed requirements of technical project. Steel structures can be protected from fire up to class R240 of fire resistance. The protective works are performed using tested and certified fire protection materials / systems.

Protection by applying vermiculite based wet-spray

We provide works for increasing fire resistance of steel structure by covering their surface with the cement-vermiculite-based masses CAFCO or FENDOLITE. Depending on situation constructions can be provided with 2, 3 or 4 – sided protection.

Our specialists will provide the customer with an ergonomic solution by offering measures in order to fulfill the designed requirements of technical project. Steel structures can be protected from fire up to class R240 of fire resistance. The protective works are performed using tested and certified fire protection materials / systems.


Warning: Invalid argument supplied for foreach() in /home/fogosauga/domains/fogo.lt/public_html/en/wp-includes/shortcodes.php on line 625

Protection by applying bio retardant solutions

We provide works for increasing fire resistance of wooden building constructions by applying ecologic antiseptic bio – retardant solutions on their surface. Our specialists will provide the customer with an ergonomic solution by offering measures in order to fulfill the designed requirements of technical project. Treated wooden structure reaches the highest European flammability class wood: B-s1, d0.

It is very important that the fire retardant should not contain volatile toxic components. In this case ecology comes along with fire safety. Healthy living environment always is the most important. Wooden structures can be protected from fire up to class R60 of fire resistance, while antiseptic bio – retardant solutions. The protective works are performed using tested and certified fire protection materials / systems.

Protection by installing Calcium-sylicate boards

There are cases when flammability class B-s1, d0 (R60) for wood constructions is not enough. Technical project can require flammability classes of A1 or A2. Then a wooden fire resistance modeled additional services are performed using hard (calcium-silicate-based) fire panels.

We provide works for increasing fire resistance of wooden structure by covering their surface with Calcium silicate boards Promatect (hard system). Depending on situation constructions can be provided with 2, 3 or 4 – sided protection. Our specialists will provide the customer with an ergonomic solution by offering measures in order to fulfill the designed requirements of technical project. Wooden structures can be protected from fire up to class R90 of fire resistance, using Promatect boards. The protective works are performed using tested and certified fire protection materials / systems.


Warning: Invalid argument supplied for foreach() in /home/fogosauga/domains/fogo.lt/public_html/en/wp-includes/shortcodes.php on line 625

Protection by installing Calcium-sylicate boards

We provide works for increasing fire resistance of steel structure by covering their surface with Calcium silicate boards Promatect. Depending on situation constructions can be provided with 1, 2 or 3 – sided protection.

Our specialists will provide the customer with an ergonomic solution by offering measures in order to fulfill the designed requirements of technical project. Concrete constructions can be protected from fire up to class R240 of fire resistance. The protective works are performed using tested and certified fire protection materials / systems.

Protection by installing mineral wool panels or applying vermiculite based wet-spray

We provide works for increasing fire resistance of steel structure by covering their surface with vermiculite-based masses CAFCO / FENDOLITE or with special mineral wool panels (density ≥120 kg / m3, binders melting temperature ≥1000 0C). Depending on situation constructions can be provided with 1, 2 or 3 – sided protection.

Our specialists will provide the customer with an ergonomic solution by offering measures in order to fulfill the designed requirements of technical project. Concrete constructions can be protected from fire up to class R240 of fire resistance. The protective works are performed using tested and certified fire protection materials / systems.

Fire protection of carbon-fibre stripes

Carbon fiber stripes are mostly designed for reinforcement  of concrete overlays. They are sticked with special thermos-resistant glue which upon thermal effects very quickly comes off in practice. Carbon stripes need less than 1000C temperature to lose adhesives, retaining properties.

Carbon fiber strips must be protected from high temperatures. Our suggested method – protection with calcium silicate base plates „Promatect”. This is one of the solutions in fire safety market even for thin and vulnerable carbon fiber. Total thickness of 80 mm provides fire resistance of EI 180 (depending on the critical temperature of the adhesive). Having a higher critical temperature adhesives require thinner protective plate thickness.


Warning: Invalid argument supplied for foreach() in /home/fogosauga/domains/fogo.lt/public_html/en/wp-includes/shortcodes.php on line 625

Suspended (false) fire rated ceilings

Fire rated suspended ceiling is a great ergonomic way to hide the engineering communications and constructions avoiding fire sealing (linear and engineering) and additional fire protection of building constructions. In this case fire safety and beauty of interior can go along..


Warning: Invalid argument supplied for foreach() in /home/fogosauga/domains/fogo.lt/public_html/en/wp-includes/shortcodes.php on line 625

Fire rated partitions

During the construction of warehouses, offices and other modern buildings have replaced easily create spaces that could be reshaped. Often there is a partition of fire-resistance problem. Ordinary gypsum not possess the necessary characteristics, and therefore the documents the fire integrity and insulation. The required degree of fire resistance required to compose lots of thick structures with mineral wool inside. Nowadays every square meter, and each centimeter worth the value of gold .

FOGO offers help in creating spaces where the bulkhead meets the most stringent fire safety requirements. Partitions can be formed with insulation or without. The boards are not only fire resistant but also have excellent acoustic properties. All material has all the necessary compliance documents.

We offer the fire partitions made of calcium silicate boards Promatect. These inner walls that provide vertical protection against fire, such as partition walls. These walls are not always bearing. Fire partition – this is the partition that the fire resistance is determined in accordance with the relevant European standards. Similarly, in accordance with the relevant flammability testing standards are determined by the behavior of materials fire surface reaction to fire. The requirement of a partition fire resistance and flammability is in the current building regulations.

Partitions may be different, depending on the destination and the desired decoration. Partitions may be composed of different types of sheet materials bonded to a metal or wooden frame with highlighted stitching or without them. They may also be manufactured by using composite panels, mounted to the frame, or is produced as a work piece and joined together with the frame or not.

When a fire spreads, it acts partition structure and trying to spread to adjoining rooms. Fire (fire resistant) partitions keep that construction disruption, and suppressing fire (prevent the spread) for a certain period

Fire rated, ultra tough DURASTEEL

During the construction of warehouses or industrial spaces, we look for ultra high mechanical durability combined with highest level of fire protection. Durasteel panels ensure both!

Fire rated glazing

No architect can imagine a house without open spaces.. Fire safety can limit architects dream projects, that’s why we offer fire rated glazing with no hard, wide, visible frames. Fire resistance up to EI120.


Warning: Invalid argument supplied for foreach() in /home/fogosauga/domains/fogo.lt/public_html/en/wp-includes/shortcodes.php on line 625

Inspection fire rated hatches (doors)

Revision doors or otherwise, Revision fire hatch for access to engineering communications, ventilation and fire protection systems, in mines or technological niches. Revision door (hatch) mounted to fire partitions and ceilings, suspended ceilings. Revision of the door to the fire resistance EI90. Revision hatch, quite versatile, covered with lid-free surface-mounted to existing structures or accurately applied to the tile covering.


Warning: Invalid argument supplied for foreach() in /home/fogosauga/domains/fogo.lt/public_html/en/wp-includes/shortcodes.php on line 625

Priešgaisrinės konvejerinių sistemų užsklandos

Until now, the architects knew that conveyor systems crossing fire-resistant structures can not be closed. It seemed unrealistic, difficult to understand. We have to admit that there was no such closer system which could be adjusted to the openings and mechanisms of conveyor systems till 2007 . Architects were designing water curtains instead. Water curtains do not limit the smoke spread, they limit temperature. And the killing element is not temperature – it’s Smoke!

Nowadays conveyer fire closers must be tested according to the standard LST EN 1366-7 „Service installations fire resistance tests. Part7. Conveyor systems and their closures requirements.“
The system is connected to the fire alarm system (GAAS). In case of fire, the system sends a signal to a central control unit, which automatically activates the fire bulkhead. The conveyor line is stopped, and the septum closes the cavity and ensures the bars and floor fire resistance. The partition may close both vertically and horizontally. Closing mechanism is always adapted to the existing situation in the Object.


Warning: Invalid argument supplied for foreach() in /home/fogosauga/domains/fogo.lt/public_html/en/wp-includes/shortcodes.php on line 625

Priešgaisriniai vartai

Revizinės durelės arba kitaip, revizinis priešgaisrinis liukas, skirtas patekti prie inžinerinių komunikacijų, ventiliacijos ir priešgaisrinių sistemų, šachtose ar technologinėse nišose. Revizinės durelės (revizinis liukas) montuojamos į priešgaisrines pertvaras ir perdangas, pakabinamas lubas. Revizinių durelių atsparumas ugniai iki EI90.